HVAC Meter PCE-DPM 3
HVAC meter PCE-DPM 3 Sintered cap to protect against moisture and dust / Data can be read out via any computer / Data memory for approx. 50,000 measurement data / CSV format / Battery can be recharged via micro-USB / Easy operation
The HVAC meter is a mobile testing device for monitoring the quality of compressed air on stationary and mobile compressed air generators. This HVAC meter measures the temperature, the relative humidity, H2O and calculates the current dew point up to an ambient pressure of 20 bar. Thanks to the sintered cap, the HVAC meter in the pressure lines is protected from dirt, moisture and high flow speeds. This increases the service life of the HVAC meter's sensors. The data memory of the HVAC meter enables the course of the measurement parameters to be recorded in a pressure line. The data recorded by the HVAC meter is permanently stored in the internal memory. The memory can be read out directly on the HVAC meter. The HVAC meter can also be connected to an operating system independent computer via the micro USB interface. This is made possible because the HVAC meter is recognized as a mass data storage device. The data saved by the pressure dew point measuring device are saved in CSV format. The stored measurement data can thus be evaluated using any spreadsheet program.
- Data storage with CSV data export
- Dew point, H2O, temperature, humidity measurement
- For inline measurement of pressure pipes
- Battery operation for mobile use
- With G1 / 2 "connection thread
- Sensors protected with sintered filters
Measurement | Temperature |
Measuring range | -10 ... 60°C / 14 ... 140°F |
Resolution | 0.01°C / 0.018°F |
Accuracy at 20°C / 68°F | -10 ... 50°C / 14 ... 122°F: ± 0.3°C / 0.5°F |
Measurement | Relative humidity |
Measuring range | 0 ... 100% |
Resolution | 0.01% |
Accuracy at 20°C / 68°F | < 5%: |
± (0.025% + 17.5% of mv) | |
> 5%: ± (1% + 5% of mv) | |
> 15%: ± (2% + 3% of mv) | |
Measurement | Dew point* |
Measuring range | -50 ... 30°C / -58 ... 86°F |
Resolution | 0.01°C / 0.018°F |
Accuracy | -40 ... 20°C / -40 ... 68°F: ± 2°C / 3.6°F |
-50 ... -40°C / -58 ... -40°F: ± 2.5°C / 4.5°F | |
*The accuracy of the dew point relates to an ambient temperature of 16 ... 25°C / 61 ... 77°F | |
Measurement | H2O |
Measuring range | 40 ... 20,000 ppm |
Resolution | 1 ppm |
Accuracy at 20°C / 68°F | ± (7.3 ppm + 8.3%) |
Environmental conditions | -10 ... 60°C / 14 ... 140°F |
0 ... 20 bar (absolute) | |
Response time at: 0.2 m / s, 1 bar, | 0 ... 40°C / 32 ... 104°F: 20s [120s] |
20°C / 68°F, 63% RH [90%] | -40 ... 0°C / -40 ... 32°F: 10s [20s] |
Data storage | For approx. 50,000 measuring points |
Adjustable storage rates | 10 seconds |
1, 5, 10, 20, minutes | |
Adjustable recording time | 1, 5, 12, 24, 48 hours |
File format | CSV |
Cable length | Approx. 1.5 m / 4.9 ft |
Thread | G1 / 2" |
Thread length | 1.2 cm |
Probe length | 5.2 cm |
Probe width | 1.2 cm |
Display | 2.3" LCD |
Power supply | Battery 3.7V DC, 3000-mAh |
Power supply power pack | |
Primary: 100 ... 240V AC, 0.25 A | |
Secondary: 5V DC, 1 A | |
Interface 7 mains connection | Micro USB |
Weight | Approx. 610 g / 1.3 lbs |
1 x PCE-DPM 3 HVAC meter
1 x USB power supply
1 x Micro USB cable
1 x Transport case
1 x Instruction manual